Alan Wire type SEU cable is used to deliver electrical service from the service head to the house meter. Compact stranded 8000 series aluminum alloy conductors. XHHW-2 insulated conductors laid in parallel. Bare conductor strands are helically wound around the two parallel conductors Glass reinforced tape is applied over the assembly. Gray PVC jacket is extruded over the entire assembly.
Available in AWG sizes #6 thru 4/0
Standards & Specifications
- UL 44 for Type XHHW-2 Conductors
- UL 854
- Federal Specification JC-30B NEC
- 8000 Series AL Alloy
- Flame Retardant Jacket
- Sunlight Resistant Jacket
Service Entrance - Style U (SUE) |
|||||
| Construction | Phase Conductor Stranding |
Ground Conductor Stranding |
Nominal Cable OD (in.) |
Ampacity 90ºC | Ampacity (Dwelling) |
| 6/2c-6g | 7 | 11 | .458 x .720 | 60 | - |
| 4/2c-4g | 7 | 16 | .505 x .811 | 75 | - |
| 4/2c-6g | 7 | 11 | .502 x .808 | 75 | - |
| 2/2c-2g | 7 | 15 | .559 x .919 | 100 | 100 |
| 2/2c-4g | 7 | 16 | .559 x .919 | 100 | 100 |
| 1/0-2c-1/0g | 19 | 18 | .661 x 1.095 | 135 | 125 |
| 1/0-2c-2g | 19 | 14 | .647 x 1.095 | 135 | 125 |
| 2/0-2c-2/0g | 19 | 18 | .719 x 1.208 | 150 | 150 |
| 2/0-2c-2g | 19 | 18 | .702 x 1.190 | 150 | 150 |
| 4/0-2c-4/0g | 19 | 30 | .857 x 1.445 | 205 | 200 |
| 4/0-2c-2/0g | 19 | 18 | .818 x 1.406 | 205 | 200 |