Type XHHW-2 conductors are primarily used in conduit or other recognized raceways for services and feeders as specified in the National Electrical Code (NEC). XHHW-2 conductors may be used in wet or dry locations. XHHW-2 conductors are rated for 600 and 1,000 volt applications. Per c(UL) specifications, RW90 conductors are rated for 600 volt applications. They are made with 8000 series aluminum alloy and cross-linked polyethylene insulation is applied. All sizes are made with a friction-reducing compound to aid in the installation process.
Available in AWG sizes #6 thru 750 MCM
Standards & Specifications
- c(UL) RW90 600V
- XHHW-2 600V/1000V
- Wet/Dry Locations (90°C)
- Underwriter’s Laboratories UL 44
- Sunlight Resistant
- Cable Tray Use 1/0 & Larger
- NEMA Publication No. WC-70
- Canadian Standard C22.2 No. 38
- Gasoline & Oil Resistant II
- ICEA S-95-658
- IEEE 1202
- ARRA 2009 Section 1605 “Buy American” Compliant
- Available in Low and High Voltage Colors
XHHW-2 Aluminum Specs | |||
Size (AWG) | Stranding | Ampacity | Weight/MFT |
#6 | 7 | 55 | 39 |
#4 | 7 | 75 | 57 |
#2 | 7 | 100 | 85 |
#1 | 19 | 115 | 109 |
1/0 | 19 | 135 | 132 |
2/0 | 19 | 150 | 161 |
3/0 | 19 | 175 | 199 |
4/0 | 19 | 205 | 244 |
250 | 36 | 230 | 293 |
300 | 36 | 260 | 345 |
350 | 36 | 280 | 397 |
400 | 36 | 305 | 449 |
500 | 36 | 350 | 551 |
600 | 58 | 385 | 674 |
700 | 58 | 425 | 774 |
750 | 58 | 435 | 824 |